Product Description

1: Compact design: it can accommodate more functional units in a smaller space;

2: Strong structure versatility, flexible assembly. The C-shaped profile with 25mm modulus can meet the requirements of various structural forms, protection levels and use environment;

3: Standard module design: can be composed of protection, operation, conversion, control, adjustment, measurement, indication and other standard units, users can choose to assemble according to needs. With more than 200 kinds of assembly parts, the cabinet structure of different schemes can be assembled and the fixed division or drawer unit can be formed.

4: Safety: a large number of high-strength flame-retardant engineering plastic components are used to effectively strengthen protection and safety performance;

5: High technical performance: the main parameters reach the contemporary international level;

6: compression site: high degree of tritization, can greatly compress the storage and transportation of prefabricated sites;

7: Easy assembly: no special complex tools are required.

Specifications

Place of Origin:

East, 1st floor, Building 2, Changan Industrial Park, 288 Wei 17 Road, Yueqing Economic Development Zone

Brand Name:

ZJYUXING

Model Number:

MNS

Certification:

图片6.png
图片7(8c44fea48b).png
Environmental conditions for use

1: The ambient air temperature is not higher than +40℃, not lower than -5℃, and the 24h average temperature is not higher than +35℃;

2: The surrounding air is clean, the relative humidity does not exceed 50% at the maximum temperature of +40 ° C, and a higher relative humidity is allowed at lower temperatures, such as 90% at +25 ° C, but it should be considered that moderate condensation may occur occasionally due to temperature changes;

3: indoor use, the altitude does not exceed 2000m;

4: where there is no significant shaking and shock vibration;

5: Pollution level: Level 3;

6: seismic intensity : Level 8;

7: The temperature during the transportation and storage of the switchgear can be between -25 ° C and 55 ° C, and the temperature can reach +70 ° C in a short time (not more than 24h);

8: If the above conditions of use cannot be met, the user and the manufacturer shall negotiate to solve the problem.

 

Technical parameter

Project

Parameter

Rated insulation voltage

690V/AC

Rated working voltage

400V/AC

Rated impulse withstand voltage

8kV

Rated frequency

50~60Hz

Maximum operating current of the main busbar

6300A

Short time withstand current of main busbar

100kA

Main bus peak withstand current

220kA

Maximum operating current of distribution busbar (vertical busbar)

1200(2000A)

Short term peak current of distribution busbar (vertical busbar)

176kA

Protection level

IP30~IP54